Sheet steel control cabinet enclosures
Choose a sheet steel control cabinet enclosure according to the drawing of the future fitting and the installation conditions. In this category you will find, among others, the designations EAE EO, EM and ET, Rittal AX and Schneider Electric NSYS3D. The presence of different series does not mean a common mounting system. For the order, the complete code, the current version and the list of supplied parts are decisive.
How to read the dimensions and scope of delivery
Distinguish the width, height and depth of the enclosure from the dimensions of the mounting plate. Manufacturers may use a different order of numbers in the name. Also measure components that protrude inward from the doors: operators, switches or connectors. Compare the sum of their depth and the depth of the opposite assembly with the design drawing, not just with the outer contour.
The specific Rittal AX 1045000 according to the manufacturer card, has outer dimensions of 400 × 500 × 210 mm and a mounting plate of 350 × 475 mm. The card lists the plate and the gland plate as included in the delivery. These data apply to the stated model; they must not be transferred to other AX enclosures or similarly sized EAE ones.
Practical procedure for designing the mounting plate
- Compile a list of devices with their dimensions and the required clearances from their documentation.
- Draw the rails, trunking, terminal rows and cable connection points.
- Verify access to the screws, labels and removable modules after complete wiring.
- Check for collisions with the hinges, lock and door-mounted devices.
- Record the planned reserve for expansion in a separate revision of the drawing.
The reserve can be expressed both as an area and as a specific free space. An equally large total area scattered between devices may not allow a single wider module to be added. In addition to the percentage, it is therefore useful to mark where a possible future assembly will actually fit.
Author's example: area versus layout
For a model plate of 300 × 400 mm, the total geometric area is 120 000 mm². If the design reserves 30 000 mm² as a reserve, that is 25 %. The calculation says nothing about the load capacity of the plate, thermal clearances or the available depth. This is an author's brief for comparing two layouts, not a recommended percentage or product dimension.
Doors, entries and surface finish
For operation, it is important whether the doors can be opened after adjacent equipment has been installed and whether the service technician can reach the terminals. When designing the wiring to the doors, take their full movement into account. Choose glands according to the cables and installation conditions; their dimensions and positions must be confirmed before the holes are made.
For a steel enclosure, also evaluate the environment with regard to the surface and intended mechanical modifications. Take the requirements for edge treatment, protective bonding and mounting of accessories from the documentation of the specific manufacturer. The mere presence of a metal plate or the colour of the surface is no proof of a correctly implemented protective function.
What to provide when requesting a replacement
State the manufacturer code, photos of the rating plate and entries, the dimension drawing and a list of accessories. An old designation with the note “replaced” is not enough to confirm mechanical conformity. Separately address cooling and heating; the dimensional requirement may not capture the thermal needs of the assembly.
FAQ
Is every enclosure supplied with a mounting plate?
Verify the scope of delivery for the selected code. Do not take the presence of a plate in an illustrative photo as a complete bill of materials.
Can I keep the old cut-outs when changing manufacturer?
Only after comparing the current drawings and mounting conditions. Similar outer dimensions alone do not confirm compatibility. For other designs, use the guide to control cabinet enclosures.