Temperature Controllers
Choose the controller from the measuring point towards the actuator. First determine whether you are monitoring the air inside the control cabinet or the process temperature with an external probe. Then choose the input type, control method and output. The same setpoint does not mean the same device: a fan is controlled differently from heating with a power element, and differently again from a device receiving a current command.
Panel thermostat or process controller?
The range includes PTM110 for heating, PTM111 for cooling and the combined PTM122. The separate EMAS datasheets distinguish an NC contact, an NO contact and an NO + NC pair; they specify DIN rail mounting. For heating, the heating must switch off when the temperature rises; for cooling, the cooling must switch on. Verify the function according to the code and the diagram, not just the colour of the knob. The catalogue labels some versions EAE, the EMAS documents; the match of the supplied revision must be confirmed.
The process part consists of ENDA ET7420, ET4430, EUC442 and EUP4420 in various power supply and communication versions. Assess the full suffix of the order code separately. When replacing, compare the label of the old and new device, including the power supply and communication interface.
Key differences between inputs
- ET7420 offers an input for Pt100 or selected thermocouples and a 72 × 72 mm front. Choose the specific probe type and the corresponding input setting.
- ET4430 also works with Pt100 and thermocouples and has a 48 × 48 mm front. Do not automatically treat its temperature input as an input for a 4–20 mA process signal.
- EUC442 according to its own manual, besides Pt100 and thermocouples it also has current inputs 0–20 and 4–20 mA. A 0–10 V input is not specified in this document.
- EUP4420 adds voltage inputs 0–10 V, 2–10 V and millivolt signals to the temperature and current inputs. For the analog input, set the conversion between the electrical signal and the displayed quantity.
Control principle and meaning of the output
ON/OFF control switches between two states; the hysteresis separates the switch-on and switch-off limits. PID changes the control action according to the size of the deviation, its duration and its trend. However, it will not eliminate an incorrectly placed probe or insufficient heating power. Before tuning the control, verify the correct direction of action and the actual process response.
ET7420 offers relay control or a command for an external SSR. EUC442 and EUP4420 also allow analog control 0–20 or 4–20 mA. With EUC442, ANL/SSR is an optional function of one output; therefore do not count the analog and logic modes as two independent channels. Do not treat the command output as the power supply of a heating element.
With EUP4420, C/A2 can be assigned to control or to the second alarm, and A1 to the first alarm or cooling. After changing the assignment, check that the required alarm function is still available. Verify versions with communication separately; a general mention of Modbus does not confirm that it is fitted in every product.
EUP4420 also offers profile control with a setpoint time program. The specification should therefore include the individual segments, dwell times and the response to a program interruption.
Mounting and finding the cause of a deviation
The ET4430 manual specifies a 45 × 45 mm cut-out and space for the connecting wires. The front dimension is therefore not the size of the opening. A thermocouple needs a suitable compensating cable; wiring a two-wire Pt100 has its own diagram. Do not transfer these instructions to other models without checking. The process controller may only be installed and electrically connected by a qualified person according to the manual of the specific version.
When diagnosing, separate three questions: does the probe measure correctly, does the controller issue the correct command and does the power section respond? First compare an implausible reading with the type and wiring of the sensor. A correct temperature on the display with heating running continuously leads to checking the output assignment and the power circuit. After replacing the probe, also re-check the behaviour when it fails.
Author's model example: conversion of 4–20 mA
Consider a transmitter set to 0–200 °C. A signal of 12 mA lies in the middle of the span: (12 − 4) / (20 − 4) × 200 = 100 °C. If the input is wrongly set to 0–20 mA, the result is 120 °C. This is our own setting model, not a parameter of the supplied probe.
FAQ
Does a reading offset fix a wrong input type?
No. Correcting one point may hide an error that reappears elsewhere in the range. First set the correct input and measuring range.
Is an SSR output the same as 4–20 mA?
No. A logic command controls the switching of an external element, while a current signal transmits a continuous demand value. The output mode and the compatibility of the receiving device are decisive.
Manufacturer documentation
PTM110 · PTM111 · PTM122 · ET7420 · ET4430 · EUC442 · EUP4420.