Noark circuit breakers
The category includes miniature circuit breakers Ex9BN and auxiliary contact AX3111. When ordering, distinguish the protective device from the signalling accessory. The range includes single-pole, two-pole and three-pole variants. The selection starts with the required function of the circuit; the same toggle appearance or a similar designation is not sufficient documentation for a replacement.
Principle: current and tripping time
A circuit breaker protects against overcurrent. With overload, both the magnitude of the current and its duration matter; with a high short-circuit current, fast tripping applies. The characteristic is therefore not a single tripping time. NOARK documentation Ex9BN states Icn 6 kA and separate B and C curves. Icn expresses the short-circuit breaking capacity, not the permissible continuous consumption.
For comparison, prepare the rated current, characteristic, number of poles and voltage. Separate steady-state operation from the short start-up of the equipment. The record “trips at start” needs to be supplemented with the duration and magnitude of the current event; a mere average over a shift may hide the decisive peak. Assessment of short-circuit conditions belongs to the professional design.
Selection without confusing the meaning of data
Read the current figure and the characteristic letter as two different pieces of information. A higher current value is not automatically a suitable fix for nuisance tripping. The cause must be known first. When replacing, compare the complete rating plate of the original device with the new one, not just the series name in the order.
Compare the number of poles with the function of the whole device. When comparing working poles, do not use the number of modules as a substitute value. For a multi-pole version, verify the documented common operation and protective functions of the individual poles. Replacement with several separate pieces cannot be justified simply by adding up their widths. Also check the coordination with other protection and the required behaviour in the event of a fault.
AX3111: position is not the cause of tripping
NOARK AX3111 has one changeover auxiliary contact; the manufacturer does not state a fault signalling contact for it. Therefore do not regard position information as separate confirmation of a short circuit. In the specification, distinguish between a position signal, a fault report and a trip command.
Mounting and handover for operation
Ex9BN is designed for a 35 mm device rail. When preparing the control cabinet, verify the space for accessories, covers, access to the operator and heat dissipation. The handover should include legible marking of the outgoing circuits and documentation of the actual fitting. The specific installation, connection and verification of the protective conditions must be carried out by a qualified person according to the device documentation and the design.
Diagnostics according to the circumstances of the event
Record which device tripped, what was running at the time and whether the event was preceded by a change in technology. Distinguish a trip immediately after start-up from a trip after longer operation. These circumstances determine further measurements, but do not prove the cause by themselves. Repeated resetting without investigating the fault does not replace diagnostics. A time record, a photo of the rating plate and a list of loads operating at the same time will help the service.
Author's model calculation: current multiple
In our own model, consider a current event of 24 A lasting 80 ms and a hypothetical circuit breaker with a rated current of 6 A. The multiple is 24 / 6 = 4, the time 80 / 1000 = 0.08 s. These two coordinates can be compared with the relevant time characteristic. The figures are a teaching brief, not a measured state or recommended protection. The calculation alone does not determine the tripping result; it needs a specific curve, its tolerance band and conditions of use.
FAQ
Can tripping be solved by changing the characteristic?
Only after assessing the cause and protective conditions. Changing the characteristic is not a universal service procedure and must correspond to the specific design.
Will a circuit breaker alone replace an RCD?
No. Overcurrent and residual current protection monitor different fault conditions. The installation design determines the required combination.
The context of the range can be found in the category Circuit breakers and RCDs. For residual current protection, continue to NOARK residual current devices.