CHINFA 12/24V DC power supplies
The designation 12/24V in the category name groups different output voltages; it does not mean that every power supply can do both. The range includes low-profile AMR versions, DRS devices and DRA, DRAN and WRA items. They differ not only in power but also in connection and input network. Choose a suitable type according to the complete order number.
Examples of items and their differences
For a smaller branch, the catalogue includes DRS1-24A with an output of 24 V DC, 1.25 A and 30 W. DRS5-24A represents a different size: 24 V DC, 5 A and 120 W. These are separate regulated AC/DC power supplies, not current steps that can be combined without further conditions.
CHINFA data sheet DRS5 distinguishes the suffix A for screw terminals and B for a pluggable connector. For DRS5-24x, it also states a reduction of the permissible current when the output voltage is increased. These marking rules cannot automatically be transferred to all other series. When ordering, always compare the complete code including suffixes.
Selection according to load and control cabinet
First separate 12V and 24V loads. Then create a current balance for the highest simultaneous operation and for start-up. A higher-power supply may not have the same dimensions or the same type of mains connection. Do not infer the connection of multiple phases from the number of output terminals.
For DRS5, the manufacturer states natural convection cooling and the dependence of permissible power on temperature and input conditions; see curves and mounting instructions DRS5. Therefore do not automatically occupy the entire free width of the rail in the design. First draw the required clearances and cable trunking. For tight installation, confirm the drawing of the specific supplied revision, including the depth of the terminals and space for bending conductors.
Model example: two modes of one machine
Assume 24V electronics with a consumption of 0.7 A and two coils of 0.25 A each. With steady-state consumption with both coils, the sum is 1.2 A. Another valve needs 0.6 A for 300 ms when switching, so 1.8 A occurs. The values given are model values. Comparison with steady-state consumption alone would lead to too tight a selection; the transient characteristic of the candidate must be verified or a solution chosen that handles the entire required simultaneous load without assumed overload capability.
The test should include the voltage at the valve and the control unit during switching. This distinguishes an insufficient power supply from a large drop on the common return conductor. The start-up of the DC load does not describe the inrush current at the mains input of the power supply.
FAQ
Can I change a 24V power supply to 12V with the adjustment element?
Not without an explicitly documented range. A trimmer is usually used for limited fine-tuning; the category name does not express universal voltage switching.
Does short-circuit protection mean that branch protection is no longer needed?
No. The behaviour of the power supply in the event of a fault must be coordinated with the conductors and branch protection. Do not infer SELV, PELV or the possibility of parallel operation from the brand alone. The general checking procedure can be found in the guide Power supplies.