Panel Meters

EMAS panel meters for displaying current, voltage, frequency, temperature or time directly on the control cabinet door. Choose by measured quantity, input (direct or via instrument transformer), supply and cut-out size.

Filters
Found 3 products
OUR TIP IN STOCK

RDH1A, EMAS, digital panel frequency meter, 30–70Hz, 220–230VAC

Cat. no.: RDH1A

The EMAS RDH1A digital panel frequency meter is used for 30–70Hz in panel measurement in industrial equipment. The specific input range and power supply are given in the table.

In stock 5 or more pcs
39,57 €
excl. VAT · 47,87 € incl. VAT
OUR TIP IN STOCK

RDV1A, EMAS, digital panel voltmeter, measurement 0–600VAC, 220–230VAC

Cat. no.: RDV1A

The EMAS RDV1A digital panel voltmeter is used for measuring 0–600VAC in panel measurement in industrial equipment. The specific input range and power supply are given in the table.

In stock 3 ks
42,14 €
excl. VAT · 51,00 € incl. VAT
OUR TIP

RDA1A, EMAS, digital panel ammeter, measurement 0–5A, 220–230VAC

Cat. no.: RDA1A

The EMAS RDA1A digital panel ammeter is used for measuring 0–5A in panel measurement in industrial equipment. The specific input range and power supply are given in the table.

On request
42,14 €
excl. VAT · 51,00 € incl. VAT

Prices include the recycling fee.

Panel Meters

Choose a panel meter according to the quantity you need to monitor and the electrical form of the input. Current, voltage and frequency are not interchangeable indicators of the machine state. The displayed value helps the operator; the contact can pass the state on to the downstream control. Before purchasing, write down separately the measured circuit, the instrument power supply and the required output response.

What the individual instruments in the range measure

  • EMAS RDH1A measures frequency in the range 30–70 Hz at an input voltage of 100–250 V AC. It is therefore suitable for assessing the frequency of AC voltage in the specified range; based on its name, it cannot be considered a universal pulse counter.
  • EMAS RDA1A is an ammeter. The separate datasheet specifies a current transformer setting of …/5 A. When selecting, you therefore also need to know the transformer ratio, not just the current of the measured line.
  • EMAS RDV1A is a voltmeter for 0–600 V AC. This range describes the measuring input, not the power supply terminals. It is not a basis for connecting a DC signal.

Wiring principle: three circuits, three different values

The datasheets of these three models specify a 230 V AC power supply and one changeover contact. The supply voltage powers the electronics, the measuring input receives the monitored quantity and the output contact changes the state of the downstream circuit. A lit display therefore does not yet confirm that the measurement is correctly wired. Likewise, the contact marking does not tell you what current may be applied to the measuring input.

When measuring current via a transformer, distinguish between the primary current of the line and the secondary current fed to the meter. The ratio of both values must match the instrument setting. Before connecting, also check the permitted burden of the transformer, including the wiring. The secondary circuit of a current transformer must not be opened during operation with current in the primary; service must follow the procedure prescribed for the specific assembly.

Choosing the output and limit states

One changeover contact does not mean two independent alarm outputs. In the specification, write what the downstream control should do when the upper limit is exceeded, when the value drops below the lower limit and when the meter loses power. Then verify whether the adjustable function of the specific version meets such a requirement. The MIN or MAX indication alone is not a description of the entire switching logic.

Assess the contact load according to the documentation of the specific unit and the type of connected load. Do not transfer the current value from the measuring range to the relay output. If you need to pass a continuous value to a PLC, require an explicitly documented analog or communication output; a changeover contact does not provide this information by itself.

Mounting and diagnostics of the measuring chain

The manufacturer specifies an eight-pin connection. Before mounting, compare the diagram of the specific model, the intended socket and the space behind the panel. The same number of pins does not prove the same wiring. Wiring must be carried out by a qualified person with the circuits disconnected; the wire marking must clearly distinguish power supply, measurement and contact.

During commissioning, compare at least several known operating points with a suitable reference meter. Record the input quantity, the display reading and the contact state at the same time. A constant ratio between the actual value and the indication leads to checking the ratio; irregular dropouts lead to checking the wiring and power supply. For non-sinusoidal voltage, first verify the suitability of the measuring method of both instruments.

Author's model example: current ratio

Consider an ideal 100/5 A transformer. With a secondary current of 3 A, the primary current is 3 × 100 / 5 = 60 A. An incorrect ratio setting of 50/5 A would correspond to 30 A for the same input. This is our own mathematical model, not a confirmation of the transformer offer or the permitted presets of RDA1A; these must be documented in its manual.

FAQ

Can electricity consumption be determined from the current?

The value in amperes alone is not enough. Energy includes power and the duration of consumption; in an AC circuit, the relationship between voltage and current also matters. An ammeter therefore does not replace an electricity meter.

Can I connect RDH1A to a pulse sensor?

Such use is not supported by the specified voltage and frequency range. First compare the electrical level, signal shape and required frequency with the documentation of a suitable counting input.