HNYU22, EMAS, top-mounted auxiliary contact block for HN contactors, 2×NO + 2×NC
HNYU22, EMAS, top-mounted auxiliary contact block with 2×NO + 2×NC contacts for HN series contactors in the 9–65A. range. An accessory, not a power contactor.
Rate 24,43 CZK per 1 EUR. Prices are indicative, invoicing is in Czech crowns.
EMAS contactors, auxiliary contacts and ELKO EP installation contactors for switching motors and other loads. Choose by current, coil voltage and contacts.
HNYU22, EMAS, top-mounted auxiliary contact block with 2×NO + 2×NC contacts for HN series contactors in the 9–65A. range. An accessory, not a power contactor.
HNYYB11, EMAS, side-mounted auxiliary contact block with 1×NO + 1×NC contacts for HN series contactors in the 17–65A. range. An accessory, not a power contactor. Supplied per 1ks.
HNYU04, EMAS, top-mounted auxiliary contact block with 4×NC contacts for HN series contactors in the 9–65A. range. An accessory, not a power contactor.
HNYU40, EMAS, top-mounted auxiliary contact block with 4×NO contacts for HN series contactors in the 9–65A. range. An accessory, not a power contactor.
HN1310NUE, EMAS: HN series power contactor, AC-3 13A, control coil 220–230VAC/50–60Hz, protection IP20. Integrated auxiliary contact 1×NO.
HN0910NUE, EMAS: HN series power contactor, AC-3 9A, control coil 220–230VAC/50–60Hz, protection IP20. Integrated auxiliary contact 1×NO.
VS120-01, ELKO EP: installation contactor with one break contact (1×NC), rated thermal current 20A, coil 24V AC/DC, DIN-rail mounting.
VS220-20, ELKO EP: installation contactor with two make contacts (2×NO), rated thermal current 20A, coil 24V AC/DC, DIN-rail mounting.
HN1710NUE, EMAS: HN series power contactor, AC-3 17A, control coil 220–230VAC/50–60Hz, protection IP20. Integrated auxiliary contact 1×NO.
HN2510NUE, EMAS: HN series power contactor, AC-3 25A, control coil 220–230VAC/50–60Hz, protection IP20. Integrated auxiliary contact 1×NO.
HN40NUE, EMAS: HN series power contactor, AC-3 40A, control coil 220–230VAC/50–60Hz, protection IP20.
HN55NUE, EMAS: HN series power contactor, AC-3 55A, control coil 220–230VAC/50–60Hz, protection IP20.
Prices include the recycling fee.
This category brings together EMAS HN power contactors, their add-on contact blocks and ELKO EP VS installation contactors. When selecting, first decide whether the device is to switch its own load or only transmit information in the control circuit. The number of contacts, current load and mechanical compatibility are three separate conditions.
For example, according to the manufacturer, EMAS HN1310NUE has an operating current of 13 A in category AC-3, a control voltage of 220–230 V at 50–60 Hz and one NO auxiliary contact. These data describe different parts of the device; see product sheet HN1310NUE. The coil voltage cannot be automatically matched to the motor power rating.
For resistive heating, check the load capacity in AC-1,; for normal motor starting and switching off during running, the AC-3 rating at the relevant voltage. The thermal current Ith alone does not confirm suitability for every switching task. When replacing, it is therefore not enough to find a higher figure in amps; the load duty, control and protective combination must also match.
NO denotes a contact that is open in the rest state, NC a contact that is closed. HNYU22 provides 2 NO + 2 NC, HNYU40 four NO and HNYU04 four NC. These versions are verified by the EMAS HN accessories overview. An add-on block extends the control contacts, not the number of main power poles of the contactor.
For an auxiliary circuit, do not assess just the number of contacts. The operating voltage, the character of the connected load and the corresponding category, such as AC-15 or DC-13 for electromagnetic control loads, are decisive. The current rating of the auxiliary contact must not be taken over from the main contactor. A standard NO/NC contact also does not automatically mean a mirror or positively driven contact for a safety function.
The range also includes VS120-01 and VS220-20. The VS series is a different design branch from the HN industrial contactors. The manufacturer describes VS220 as a two-contact installation device with several contact combinations; see ELKO EP documentation VS220. Always identify the required coil and contact configuration from the complete order designation.
Therefore do not choose a spare part by module width or identical rated current. For electronically powered appliances, light sources or motors, switching conditions other than those for a resistive load may be decisive. Verify the intended use of the specific model in its load data.
Before adding a block, check the designated series, contactor size, fixing method and space after fitting. Side and front accessories may have different restrictions. Mechanical snapping-in is not in itself proof of the correct combination; nor can parts be automatically transferred between brands. A separate selection for another platform is offered by Siemens contactors.
For a motor feeder, also assess EMAS motor protection. The contactor does not replace it, and adding an auxiliary contact does not create overload protection. Verification of coordination belongs to the specific design, not to the general description of the product series.
The project needs three independent make signals and one break signal. The contactor under consideration has one free auxiliary NO. After verifying compatibility, a block with 2 NO + 2 NC can create a total of three NO and two NC; one NC therefore remains in reserve. A block with four NO alone does not meet the requirement for a break contact. This is a logical balance, not a wiring diagram or confirmation of the permissible load.
No. Also check the function of the contacts at rest, the voltage and type of coil supply, the utilisation category, dimensions and accessories. The same number of terminals does not mean an identical device.
No. An auxiliary contact only switches its circuit according to the mechanical state of the device. It does not monitor motor current like overcurrent protection; the overall division of functions is explained in the guide to contactors and motor protection.
We need technical cookies for the cart and checkout to work — these are always used. Analytics cookies show us which pages people look for and where they get lost, and help us improve the shop. We only use them if you allow it. More in the data processing policy.
Choose which cookies we may use. You can change your choice at any time.
They keep the cart contents, your login and selected language, and protect forms from abuse. An order cannot be completed without them, so they are used even without consent.
Google Analytics shows us traffic and behaviour on the website in aggregated form. This tells us which pages are not working for people. We do not identify anyone from this data.