Phone +420 774 723 123 Cart · 0 · empty

PULS 24V DC Power Supplies

PULS 24 V DC DIN rail power supplies with high efficiency, power reserve for load start-up and DC-OK signalling. Choose by output current, supply network and width on the rail.

Filters
Found 1 products

PIC120.241C, PULS, power supply PIC120, 24VDC/5A, 120W, DIN, DC-OK contact

Cat. no.: PIC120.241C

PIC120.241C, PULS, power supply PIC120, 24VDC/5A, 120W, DIN, DC-OK contact. PULS PIC120.241C is a single-phase power supply with an adjustable output of 24–28VDC.

On request
64,24 €
excl. VAT · 77,73 € incl. VAT

Prices include the recycling fee.

PULS 24V DC power supplies

In this branch you will find PIC120.241C. The following specific data apply to this order code, not to the entire PULS range. When comparing similar names, keep the final suffix; another model may have a different input or equipment.

Output, input network and adjustment

PIC120.241C is a single-phase power supply with a rated output of 24 V DC, 5 A and 120 W. The PULS data card states an AC input of 200–240 V with a tolerance of ±10 %. It is therefore not a universal device for a 100–240 V network. The same card states an output adjustment of 24–28 V and a current of 4.3 A at 28 V. Raising the voltage does not create additional power.

For the project, check the actual input conditions, not just the usual mains voltage at the site. The mains supply must correspond to the exact instructions. For any other method of supply, it is not enough to assume that a similar-looking power supply of the same brand supports it.

Derating as a specific design condition

The manufacturer specifies a power reduction of 3 W for each degree between +55 and +70 °C; the conditions are given in card PIC120.241C and the Environment chapter of the data sheet. Ventilation, mounting position and the temperature at the device therefore directly affect the usable output.

Model example for a warmer control cabinet

Assume standard permitted mounting, other data sheet conditions met and an ambient temperature of +65 °C. The calculation according to the stated rule is 120 − 3 × (65 − 55) = 90 W. At a setting of 24 V, this corresponds to 3.75 A. A hypothetical load of 4 A already exceeds this thermal budget, although it would seem acceptable when looking only at the 5 A designation.

The design solution may be a lower load, a different thermal arrangement or a more suitable power supply. It cannot be relied on that any overtemperature protection will replace correct sizing. The example does not confirm the function of a specific enclosure without temperature measurement and installation checks.

Switch-on, signalling and mechanical compatibility

Data sheet PIC120.241C describes limitation of the input inrush current using an NTC and a DC-OK relay contact. According to the card, the housing dimensions are 39 × 124 × 124 mm; the space for the rail, conductors and cooling must be assessed in addition. Also use the PULS mounting and electrical conditions when designing the protective connection.

Connect DC-OK according to the permissible contact load and evaluation threshold. Its state does not prove the voltage at a remote load: a faulty connection or long wiring can cause a local problem while the power supply otherwise works correctly. When several units are switched on together, check the mains inrush current of the whole group separately from the start-up of the DC loads.

FAQ

Can I use PIC120.241C as a charger?

The manufacturer does not permit battery charging with this power supply in the data sheet. An adjustable output is no proof of a suitable charging mode.

Are 120 W available under all circumstances?

No. Assess the temperature, voltage setting and other operating conditions. The calculation of the whole branch, including continuous consumption and peaks, can be found in the guide Power supplies.

Cookies on this website