NOARK contactors
The NOARK range brings together industrial contactors Ex9C, modular installation relays Ex9CH20 and installation contactor Ex9CH40. It is not a single design graded by current. The right choice is based on the load, the required number of contacts, the control voltage and the mode of operation; only then does it make sense to compare size and space in the control cabinet.
Ex9C for industrial motor switching
The difference between current categories is shown by Ex9C18: the manufacturer states 32 A in AC-1, but 18 A in AC-3 at 380/400 V and a corresponding motor power of 7.5 kW. The data belong to specific operating conditions, not to every voltage. The source is the Ex9C contactor data sheet. The coil voltage is selected separately.
AC-3 accounts for motor starting and switching off during running. With jogging or plugging, the stress is different and the corresponding category and service life must be assessed. The higher permissible current for a resistive load is not a reserve that can be freely used for a motor.
Ex9CH20 and installation contactors are not the same
Ex9CH20 are installation relays with various contact combinations. The manufacturer distinguishes 20 A for AC-1/AC-7a and 9 A for AC-7b; at the same time, the voltage and version of the specific product must be respected. The distinction is given in the Ex9CH20 installation relay data sheet. The marking “20 A” alone is therefore not enough to assess a motor load.
The Ex9CH series is intended for modular installation applications and offers different current and contact versions; see the overview of Ex9CH installation contactors. This category also includes the Ex9CH40. version. When switching from a relay to a contactor, check the function of the individual contacts, their number and the control voltage, not just the current on the front label.
Coil and contact logic
In the requirement, separate the voltage of the switched load from the control voltage. The figure 230 V in the order designation may denote the coil, not the limit of the motor circuit. The connected control output must meet the coil requirements; the operating voltage, frequency and type of supply are verified for the specific variant.
Distinguish between main poles and auxiliary contacts. The requirement “three poles and one auxiliary NO” does not mean four identical power paths. Compare the contact logic with the original device and with the de-energised state. When replacing an installation relay with a break contact, a variant with make contacts only cannot be used without review.
Protection and mechanical fitting
A contactor by itself does not handle motor overload or universal short-circuit disconnection. Assess the required protective assembly together with NOARK motor starters. Short-circuit coordination cannot be proven just because both parts carry the same logo; it depends on their exact types and the conditions given in the combination documentation.
When planning the layout, allow for heat losses, added accessories and access for maintenance. The dimensions of the basic device alone may not be enough for the whole assembly. The wider context of selection is given in the category Contactors and motor protection.
Model example of two different requirements
Consider two separate tasks at 400 V: a normally switched motor with a rated-plate current of 17 A and a resistive load with a current of 20 A. For Ex9C18 the motor is compared with the rating of 18 A in AC-3, while the resistive load is compared with 32 A in AC-1. Both comparisons work out preliminarily in terms of current, even though the second load exceeds the number 18 in the designation. The other conditions still need to be verified; the example does not confirm a specific implementation or protective combination.
FAQ
Can the AC-1 current be used for any appliance?
No. The character of the load and the switching method must match the category. Special starting or charging currents cannot be assessed from the rated consumption alone.
Does a single contactor automatically provide a safe stop?
The switching function alone does not justify such a conclusion. The required safety behaviour must be documented by the design and verification of the entire relevant part of the control system.