Allen-Bradley Power Supplies

Allen-Bradley (Rockwell Automation) 1606 series power supplies for control systems and cabinets. Choose by output voltage and current, supply network and DIN rail mounting.

Filters
Found 0 products

Prices include the recycling fee.

Allen-Bradley power supplies

When choosing the power supply for an Allen-Bradley assembly, the specific control system and its power architecture are decisive, not just the same brand on the devices. This guide will help you prepare documentation for selecting or replacing a power supply. The examples of manufacturer documentation given are not confirmation of the current range or availability of individual models.

An external power supply is not automatically a bus supply

An external regulated power supply supplies energy to a designated input of the equipment. The internal bus supply may only be created by the adapter or a special system module. A specific example is given in the Rockwell Automation documentation for PointMax: it distinguishes the supply of modules, bus, sensors and actuators. Do not transfer this breakdown or its limit values to another platform without verification.

For standalone switched-mode power supplies, use as orientation the Bulletin 1606 technical data. This is manufacturer documentation, not confirmation of the TECHNOLINE range. When replacing, start with the complete order number including the suffix and device revision.

How to compile documentation for selection

  • From the documentation of the adapter, CPU and I/O, determine all power inputs. Separate the electronics' own consumption from the loads connected to the outputs.
  • Record the required voltage, tolerance, highest operating current and start-up requirements. Also monitor the permissible load of feed-through terminals.
  • Verify the requirement for SELV or PELV for the specific circuit. The same voltage value does not prove protective separation.
  • Compare the network type, input inrush current, protection, temperature limitations and any fault signalling. The DC-OK parameter is only meaningful with a known function and wiring.

Mechanical replacement and operating conditions

The same housing width is not enough. Check the support rail, depth, terminal position, space for conductors and ventilation clearances. The new power supply must not change the airflow so that adjacent devices fall outside the permissible conditions. Compare the required current with the value valid at the actual temperature and mounting position, not just with the front label.

Model example of separate budgets

A hypothetical assembly has electronics consuming 0.8 A and actuators with a maximum simultaneous load of 2.4 A on the same 24 V branch. The power supply must provide at least 3.2 A under the given conditions, even before considering start-up and future expansion. However, if the feed-through path to the actuators has a model limit of 2 A, a stronger power supply will not raise this limit. The distribution must be redesigned according to the system documentation. The figures given are not parameters of PointMax or Bulletin 1606.

Frequently asked questions and mistakes

Can the power supply be replaced with another brand?

It may be possible, but it is not an automatic replacement. Besides voltage and current, the requirements for start-up, protective separation, outages, protection and signalling must match. An overview of other principles is offered by Power supplies; for example CHINFA 12/24V DC power supplies are a different catalogue branch, not a pre-approved replacement.

Is the rated current of an output module its consumption?

No. It expresses the permissible load of the output under specified conditions. The balance includes the loads actually supplied and the module's own consumption according to its manual.