Siemens contactors
The Siemens range includes power contactors, auxiliary contactors and separate accessories. Therefore do not select the 3RT and 3RH series as interchangeable devices with the same number of contacts. For replacement, the complete order code, size, control voltage and function of the individual circuits are important; the SIRIUS designation or the appearance of the front alone is not enough.
Power 3RT and auxiliary 3RH
For the 3RT2016-1BB42 on offer, the manufacturer states 9 A in AC-3e/AC-3, a motor power of 4 kW at 400 V, three main poles, 24 V DC control and one auxiliary NC. The parameters relate to this order number; see the Siemens 3RT2016-1BB42 data sheet. A different suffix may change the control or the version.
Auxiliary contactor 3RH2131-1AB00 has a 3 NO + 1 NC combination and a 24 V AC coil. It is intended for control functions; the current ratings of its contacts are assessed in the relevant auxiliary circuit categories, not as the power AC-3 rating of a three-pole motor contactor. The source is the auxiliary contactor data sheet 3RH2131-1AB00.
What current, power and voltage actually mean
The current for AC-1 and the motor current for AC-3 are not interchangeable values. The power in kW is linked to the specified voltage and type of motor duty. If you keep only the power when replacing, you may overlook a different control voltage, number of auxiliary contacts or a more demanding switching duty.
Also assess starting, switching off during running and the frequency of short commands. Demanding jogging is not the same as occasionally switching on a fan. Formulate the requirement according to the actual machine cycle; the mechanical number of operations alone does not prove electrical life under a specific load.
Coil, suppression and compatible accessories
The designations 24 V AC and 24 V DC cannot be interchanged just because the numerical value matches. The control output must suit the coil type and its consumption in the individual states. Before adding suppression, check whether the version already includes it, which element the manufacturer permits and how it affects the contactor drop-out.
For example, 3RT2916-1DG00 is a diode suppressor for 12–250 V DC, intended for the listed series 3RT2.1 and 3RH2. It is not a universal module for every Siemens coil; the assignment is given in the suppressor diode data sheet. Similarly, select add-on contact blocks according to the exact design series and the prescribed location.
Different generations of accessories appear in the range. The same size or similar first characters of the code do not confirm mechanical interchangeability. A separate category is dedicated to another platform Contactors and auxiliary contacts; its parts cannot be transferred to Siemens without documented assignment.
Mounting and protective assembly
Check the space after adding accessories, access to the terminals and the thermal situation in the control cabinet. Assess the installation conditions according to the exact variant and its documentation. The mounting dimension of the basic body may not correspond to the envelope of the whole fitted combination.
A contactor does not replace overload and short-circuit protection. The specific feeder must have designed protective devices and verified coordination; neither the brand nor the AC-3 category constitutes such verification. The division of functions is explained in the parent category Contactors and motor protection.
Model example of checking a spare part
Consider a machine with 24 V DC control, a three-phase 400 V motor and a rated-plate current of 8 A, which is switched off after starting during normal running. In terms of these selected data, 3RT2016-1BB42 with a rating of 9 A in AC-3. can be assessed preliminarily. By contrast, 3RH2131-1AB00 is not a suitable replacement: it is an auxiliary device with a different contact function and an AC coil. The example does not verify protective coordination or the permissible operating load of the complete equipment.
FAQ
Does an auxiliary contact prove that the motor is actually disconnected?
Not automatically. For the required feedback, the properties of the specific contact and the evaluation design must be verified. The NO or NC designation alone does not guarantee a safety function.
Can I add any suppressor?
No. The type of supply, voltage range, design assignment and required timing behaviour are decisive. Verified accessories are part of the correct specification, not an optional substitute for professional design.