Complete relays with socket

For a complete relay with socket, assess the finished assembly as one functional unit and at the same time record its individual parts. The designation “complete” must be supplemented by a list of the parts supplied. Before ordering, therefore have it determined whether the assembly contains only the relay and base, or also a clip, indication, protective module and label.

Deciding by scope of delivery

Start with the required control signal and the list of switched circuits. Then compare the overall dimensions, terminal positions and service requirements. If you are putting together your own combination, documentation can be found in the categories Relay, Sockets and Accessories. Select the individual items according to documented compatibility, not merely mechanical insertion.

In the order brief, write one row for the functional unit and further rows for its contents. For each, state whether it is a required part or a verified component of the pack. Such a breakdown reveals a missing clip or an unnecessarily ordered module before the bill of materials is finalised.

Principle: assembly input and inserted relay

RELPOL interface documentation explicitly distinguishes the voltage of the assembly input and the voltage of the inserted working relay. They need not be identical, because the socket may contain electronics. When replacing, therefore determine the replacement relay according to the assembly's compatibility table; the data on the external input terminals alone is not enough.

Describe the contact circuit separately: voltage, current, type of load and duty cycle. A completed input figure does not close the output selection. When comparing two assemblies, also include the functional diagram so that it is clear whether their individual terminals perform the same tasks. A photo helps with identification but does not contain all this information.

Author's model example: space on the rail

For a practice layout, let us choose ten assemblies 8 mm wide, two separating gaps of 12 mm each and a service reserve of 20 mm. The required length is 10 × 8 + 2 × 12 + 20 = 124 mm. All dimensions are the author's assumptions, not parameters of the product offered or recommended mounting spacings.

The example shows why the sum of the housing widths is not the total length of the installation. Before actual mounting, replace the practice values with the data of the selected assembly and the control cabinet drawing. Separately check the space in front of the terminals and the path needed to remove the relay. These requirements are not reflected in the rail length by themselves.

Mounting and handover of the assembly

At handover, link the designation in the diagram with the visible marking on the assembly. Store the list of inserted parts, their order codes and the relevant edition of the documentation. The mounting procedure must respect the specific terminals and manufacturer conditions. Do not take over prescribed gaps, cross-sections or torques from a similar-looking base.

Diagnostics after replacement

If the fault appeared immediately after replacement, first compare the identification of the original and new part. Also record which components of the assembly remained in place. This makes it possible to distinguish an insert selection error from a change in the wiring. Electrical verification and safe securing of the equipment are carried out by a qualified person.

FAQ

Does every assembly contain a protective module?

The specific scope of delivery and diagram are decisive. Do not infer this equipment from the word “complete” alone.

Can only the relay be replaced during servicing?

First verify whether the assembly manufacturer allows it and which replacement code it prescribes. Keep the link between the replacement part and the original assembly in the bill of materials.

Cookies on this website

We need technical cookies for the cart and checkout to work — these are always used. Analytics cookies show us which pages people look for and where they get lost, and help us improve the shop. We only use them if you allow it. More in the data processing policy.