EKM1-OF, CHANGAN, auxiliary contact for circuit breakers EKM1-63, 1NO + 1NC contact
EKM1-OF CHANGAN – auxiliary contact for circuit breakers EKM1-63, 1NO + 1NC contact. Exact technical data for selecting the circuit breaker accessory type.
Kurs 24,39 Kč za 1 EUR. Ceny są orientacyjne, rozliczenie następuje w koronach czeskich.
Accessories for CHANA EKM1 circuit breakers – auxiliary contacts for position indication, undervoltage releases and shunt trips. Check compatibility with the breaker series and the mounting method.
EKM1-OF CHANGAN – auxiliary contact for circuit breakers EKM1-63, 1NO + 1NC contact. Exact technical data for selecting the circuit breaker accessory type.
Ceny zawierają opłatę recyklingową.
Accessories for CHANA circuit breakers extend the possibilities of the assembly but do not change the basic purpose of the circuit breaker. This subcategory contains auxiliary contact EKM1-OF designated 1NO+1NC. Its task is to pass information about the state to a signalling or control circuit. The selection therefore combines two questions: mechanical compatibility with the circuit breaker and electrical suitability for the connected input or load.
The manufacturer's ETEK overview of accessories for the S1 series distinguishes an ordinary auxiliary contact linked to the mechanism position from an alarm contact. This is important when designing the operator screen: the message “off” must not automatically mean “short circuit”. Auxiliary signalling alone is also not confirmation of a de-energised state.
The designation 1NO+1NC denotes one make and one break contact. Verify the state relative to the mechanism position, the terminal marking and the connection to the main device in the specific diagram. Do not transfer terminal numbers from other accessories just because they have a similar number of contacts.
For the assembly, require the accessory type to match the exact version of the main device. Compare the mounting side, coupling mechanism, permitted combination of add-ons and the total width. In an already fitted control cabinet, verify not only the space on the rail but also the accessibility of the terminals and the routing of new signal conductors.
The basis of the order should be the full code of the circuit breaker, the event to be reported and the diagram of the signalling circuit. A photo of the front helps with identification but does not prove all conditions of mechanical compatibility. First confirm the suitable add-on in the manufacturer's documentation.
The current of a PLC digital input is not the same task as directly switching a coil or indicator lamp. Record the voltage, type of current and character of the connected load; look up the corresponding permissible contact load for them. A single general value in amps without conditions is not sufficient documentation. Also check any minimum load and the requirements of the connected input.
Consider a model PLC input that has the value 1. when the circuit breaker position is confirmed. The value 0 may mean another position, but also loss of auxiliary power or an interruption of the signalling line. The program should therefore not display a specific fault cause without further information. The designer must determine which states the system distinguishes and what remains a common report.
If it is necessary to distinguish manual switch-off from a protective trip, the requirement must be explicitly stated in the brief. Merely renaming the message in the program does not create such information. This example explains the information logic; it is not a wiring diagram or a safety function design.
A qualified person verifies the mechanical coupling, connection and the actual meaning of each signal in the permitted operating states. The results belong in the documentation together with the descriptions of terminals and inputs. In the event of a discrepancy between the screen and the local position, check the entire signalling chain, not just the contact itself. Do not use the display reading as a substitute for the prescribed verification procedure when safely securing the workplace.
No. It adds a signalling function, not a higher electrical capability of the main current path.
No. The coupling to the circuit breaker, dimensions, terminals and load conditions must also match. To select the main device, return to the CHANA overview.
Techniczne pliki cookies są potrzebne do działania koszyka i zamówienia — są używane zawsze. Analityczne pliki cookies pokazują nam, których stron ludzie szukają i gdzie się gubią, i pomagają nam ulepszać sklep. Użyjemy ich tylko wtedy, gdy na to pozwolisz. Więcej w zasadach przetwarzania danych.
Wybierz, których plików cookies możemy używać. Wybór możesz w każdej chwili zmienić.
Przechowują zawartość koszyka, logowanie i wybrany język oraz chronią formularze przed nadużyciem. Bez nich nie można złożyć zamówienia, dlatego są używane także bez zgody.
Usługa Google Analytics pokazuje nam ruch i zachowanie na stronie w formie zbiorczej. Dzięki temu wiemy, które strony nie działają dla ludzi. Na podstawie tych danych nikogo nie identyfikujemy.