EKM1-63-1P-16A/B, CHANGAN, miniature circuit breaker, 1P, 16A, characteristic B, 6kA
EKM1-63-1P-16A/B, CHANGAN: miniature circuit breaker 1P/16A with tripping characteristic B and declared breaking capacity 6kA.
Kurs 24,39 Kč za 1 EUR. Ceny są orientacyjne, rozliczenie następuje w koronach czeskich.
CHANA EKM1 miniature circuit breakers for AC circuits with B or C characteristic in one- to four-pole versions. Choose by rated current, characteristic, number of poles and breaking capacity.
EKM1-63-1P-16A/B, CHANGAN: miniature circuit breaker 1P/16A with tripping characteristic B and declared breaking capacity 6kA.
EKM1-63H-1P-02A/B, CHANGAN: miniature circuit breaker 1P/2A with tripping characteristic B and declared breaking capacity 10kA.
EKM1-63H-1P-04A/B CHANGAN – circuit breaker 1-pole, 4A, characteristic B, 10kA, 04 A. Key data: EKM1-OF. Exact technical data for selecting the miniature circuit breaker type.
EKM1-63H-1P-10A/B CHANGAN – circuit breaker 1-pole, 10A, characteristic B, 10kA, 10 A. Key data: Value. Exact technical data for selecting the miniature circuit breaker type.
EKM1-63-1P-02A/C CHANGAN – circuit breaker 1-pole, 2A, characteristic C, 6 kA, 2 A, 6kA. Key data: Value. Exact technical data for selecting the miniature circuit breaker type.
EKM1-63H-1P+N-04A/B, CHANGAN, Miniature circuit breaker 1P+N, 4A, characteristic B, 10kA. This circuit breaker of the EKM1-63H series protects the circuit against overcurrent and short circuit.
EKM1-63H-3P-16A/C, CHANGAN, Miniature circuit breaker 3P, 16A, characteristic C, 10kA. This circuit breaker of the EKM1-63H series protects the circuit against overcurrent and short circuit.
EKM1-63-1P+N-04A/B, CHANGAN, Miniature circuit breaker 1P+N, 4A, characteristic B, 6kA. This circuit breaker of the EKM1-63 series protects the circuit against overcurrent and short circuit.
EKM1-63-1P+N-10A/B CHANGAN – circuit breaker 2-pole, 1P+N, 10A, characteristic B, 6kA, 2 (1P+N), 10 A. Key data: EKM1-OF. Exact technical data for selecting the miniature circuit breaker type.
EKM1-63H-3P-16A/B, CHANGAN: miniature circuit breaker 3P/16A with tripping characteristic B and declared breaking capacity 10kA.
Ceny zawierają opłatę recyklingową.
Choose an AC circuit breaker as part of the protection of the whole circuit. It must match the cable, the character of the load and the fault conditions at the installation point. The CHANA range includes EKM1-63 and EKM1-63H variants with different currents, characteristics and pole arrangements. Finding the same figure in amps is therefore only the first step, not confirmation of a suitable replacement.
For the series EKM1-63 the manufacturer describes a thermal and an electromagnetic release. The thermal part handles overload, the electromagnetic part the fast response to high overcurrent. It is not a precise current limiter that trips immediately when the rated value is exceeded by an arbitrarily small amount. The time-current characteristic is essential for assessing a specific event.
For the electromagnetic zone, the manufacturer states a range of 3–5 × In for B and 5–10 × In for C. A higher multiple does not generally mean better protection. It corresponds to a different response to short-term current peaks and at the same time affects the fault current requirements for fast disconnection. A change of characteristic must be assessed by a specialist according to the actual circuit.
Author's numerical example: for a model 10 A circuit breaker, the stated multiples correspond to bands of 30–50 A for B and 50–100 A for C. This is just a conversion of the magnetic zone, not a complete tripping curve or a design of load protection. For example, it does not determine the response time for long-term slight overload.
Do not compare operating amps directly with the kiloamps stated for breaking capacity. The first value relates to the current size of the device, the second to interrupting a short circuit under defined conditions. For the EKM1-63H version always verify the complete specification of the specific variant. The suffix alone does not replace checking the voltage and pole arrangement.
A useful service record contains the moment of switch-on, the simultaneous operation of loads, the operating time before tripping and any changes in the installation. The difference between immediate tripping and a fault after warming up can help with diagnostics, but does not prove the cause by itself. Without measurement, it cannot be decided whether it is an overload, a fault in the connected equipment, a connection problem or another condition.
Mounting and checking of connections are carried out by a qualified person according to the specific instructions. Do not replace the device with a higher current value just to stop it tripping. This could change the relationship between the protection and the protected cable.
No. Require explicit DC parameters and permitted wiring for the exact product. Separate orientation is offered by the DC circuit breakers category.
An ordinary circuit breaker has no residual protective function. The need for an RCD or a combined device is determined by the installation design, not by matching current values.
Techniczne pliki cookies są potrzebne do działania koszyka i zamówienia — są używane zawsze. Analityczne pliki cookies pokazują nam, których stron ludzie szukają i gdzie się gubią, i pomagają nam ulepszać sklep. Użyjemy ich tylko wtedy, gdy na to pozwolisz. Więcej w zasadach przetwarzania danych.
Wybierz, których plików cookies możemy używać. Wybór możesz w każdej chwili zmienić.
Przechowują zawartość koszyka, logowanie i wybrany język oraz chronią formularze przed nadużyciem. Bez nich nie można złożyć zamówienia, dlatego są używane także bez zgody.
Usługa Google Analytics pokazuje nam ruch i zachowanie na stronie w formie zbiorczej. Dzięki temu wiemy, które strony nie działają dla ludzi. Na podstawie tych danych nikogo nie identyfikujemy.