SMOWO strain gauge amplifiers with analogue output or Modbus communication. Choose by input, output and supply.
RW-ST01A SMOWO – strain gauge amplifier. Industrial product for automation, measurement and control.
RW-ST01D SMOWO – strain gauge amplifier. Industrial product for automation, measurement and control.
RW-GT01A SMOWO – strain gauge amplifier. Industrial product for automation, measurement and control.
RW-GT01D SMOWO – strain gauge amplifier. Industrial product for automation, measurement and control.
RW-GT01DE SMOWO – strain gauge amplifier. Industrial product for automation, measurement and control.
Ceny zawierają opłatę recyklingową.
An amplifier links the small measuring signal of the sensor with the analogue input or communication of the control system. The range includes SMOWO RW-ST01A and RW-GT01A analogue transmitters as well as RW-ST01D, RW-GT01D and RW-GT01DE versions with a RS485/Modbus. interface. When choosing, address the sensor connection, the required transmission method and the location of the electronics separately.
The mV/V value expresses the sensitivity of the sensor relative to excitation; it does not denote a finished voltage output. The amplifier must accept the corresponding differential signal including zero offset and, where applicable, the opposite polarity under tension or reverse torque. Check the sensitivity in the documentation of the selected strain gauge sensor; u torque sensor proceed in the same way. The same brand alone does not guarantee the input range.
The RW-GT01A sheet states an input for a sensitivity of 2.0 mV/V ±10 %. For wiring, it also distinguishes E+/E− for excitation and S+/S− for the signal; the letter S here does not mean a separate sense pair. The basis is SMOWO RW-GT01A datasheet. A different sensitivity cannot automatically be solved merely by changing the scale in the PLC if the transmitter itself does not process the required signal correctly.
RW-ST01A, according to the manufacturer, has a 4–20 mA current output and a 0–5 or 0–10 V voltage output; the supply is a separate value. The manufacturer distinguishes zero and full-scale settings for the current and voltage output. The specific terminals and setting elements are described in dokumentace RW-ST01A. On the PLC side, the input type and the set range must match. Do not connect the current output as a voltage signal without a corresponding input circuit.
For RW-GT01DE, the manufacturer states Modbus RTU, 5 V sensor excitation, adjustable conversion rate and software filtering. These properties relate to the specific type; see RW-GT01DE documentation. For commissioning, you also need the correct device address, transmission parameters and register map for the given version. Before interpreting the number, verify the unit, sign and data format used.
The transmitter supply voltage is not the bridge excitation voltage. Assess the excitation load capacity according to the input resistance of the connected sensors; several bridges in parallel mean higher consumption. Such a connection requires a separate design and is not automatically suitable for independent measurement of individual points.
Four-wire wiring carries excitation and signal; six-wire adds sense and requires a corresponding input. Handle jumpers and shielding according to the manual. Provide cable strain relief and separate signal lines from power lines. For the module, verify dimensions, fixing and access to the terminals.
Assume an already verified linear assembly for 0–1000 N, set to 4–20 mA. The conversion to force is F = (I − 4 mA) / 16 mA × 1000 N. A value of 12 mA represents 500 N and 18.4 mA represents 900 N. If the program mistakenly used a range of 0–20 mA, it would display 600 N at 12 mA. The example illustrates a configuration error, not the accuracy of a specific amplifier. After setting up, carry out a check with a known load, not just a check of the numbers in the program.
No. Zeroing adjusts the starting point, tare subtracts a chosen preload. Calibration establishes the relationship between the indication and reference values including uncertainty. Also check the full-scale setting at an intermediate point; a correct zero will not reveal a gain error.
Not necessarily. You may repeatedly read the same sample. Conversion, filter, communication and the PLC program are decisive. To capture peaks, verify the response of the entire chain on a representative waveform; the number of bits of the converter alone does not prove the required speed or accuracy.
Techniczne pliki cookies są potrzebne do działania koszyka i zamówienia — są używane zawsze. Analityczne pliki cookies pokazują nam, których stron ludzie szukają i gdzie się gubią, i pomagają nam ulepszać sklep. Użyjemy ich tylko wtedy, gdy na to pozwolisz. Więcej w zasadach przetwarzania danych.
Wybierz, których plików cookies możemy używać. Wybór możesz w każdej chwili zmienić.
Przechowują zawartość koszyka, logowanie i wybrany język oraz chronią formularze przed nadużyciem. Bez nich nie można złożyć zamówienia, dlatego są używane także bez zgody.
Usługa Google Analytics pokazuje nam ruch i zachowanie na stronie w formie zbiorczej. Dzięki temu wiemy, które strony nie działają dla ludzi. Na podstawie tych danych nikogo nie identyfikujemy.