RPS-15-24, Rievtech, switched-mode DIN-rail power supply, 24VDC/0.63A, 15W
RPS-15-24, Rievtech: DIN-rail power supply for powering automation, output 24VDC/0.63A, 15W, input 85–264VAC.
Tipo de cambio 24,43 Kč por 1 EUR. Los precios son orientativos; la facturación se realiza en coronas checas.
Rievtech RPS and RPS-S series DIN rail power supplies for powering PLCs, relays and sensors. They are an affordable choice for smaller cabinets. Choose by output voltage and current with reserve for inrush peaks.
RPS-15-24, Rievtech: DIN-rail power supply for powering automation, output 24VDC/0.63A, 15W, input 85–264VAC.
RPS-15-S24 – Rievtech – slim switched-mode DIN-rail power supply, 24VDC/0.65A, 15W, input 90–264VAC. DIN rail, efficiency 84.5%, operation −25 to +70°C, dimensions 103.7×32×97.5mm.
RPS-45-24, Rievtech, industrial switched-mode DIN-rail power supply: output 24VDC/2A (48W), input 85–264VAC, output adjustment 21.6–26.4VDC.
The Rievtech power supply RPS-60-24 creates a regulated output of 24VDC for supplying control circuits. It continuously delivers a rated current of 2.5A; for this model, the manufacturer states 60W.
RPS-60-S24, Rievtech, switched-mode DIN-rail power supply, 24VDC/2.5A, 60W. Model S24 of the RPS-60-S series provides DC power for control circuits with an output current of 2.5A.
RPS-100-24 – Rievtech – switched-mode DIN-rail power supply, 24VDC/4A, 96W, input 85–264VAC. DIN rail, efficiency 87%, operation −20 to +60°C, dimensions 100×93×56mm.
RPS-U120S24 – Rievtech – high-power switched-mode DIN-rail power supply, 24VDC/5A, 120W, input 90–264VAC. DIN rail, efficiency 88%, operation −20 to +70°C, dimensions 124×119×45mm.
Los precios incluyen la tasa de reciclaje.
The category contains RPS-15-24, RPS-15-S24, RPS-45-24, RPS-60-24, RPS-60-S24, RPS-100-24 and RPS-U120S24. The complete code, including the letter S and its position, is essential for selection. The series name alone does not guarantee specific power, dimensions or the same overload behaviour.
A switched-mode AC/DC power supply creates a regulated DC supply for compatible loads. It is not a communication accessory that would ensure PLC compatibility by itself. The connected unit must have a suitable supply input, polarity and permissible voltage range. Count the current of loads switched by relay contacts only in the branch from which they are actually supplied.
The catalogue RPS-60-24 and RPS-60-S24 are listed with the same output of 24 V DC, 2.5 A and 60 W, but different housing dimensions. Before replacing, therefore check the installation profile and cable reach. The product groups are also distinguished in the manufacturer's official RPS overview; not all its variants are automatically part of this category.
For each power supply, distinguish the mains input from the regulated output. For example, 24 V DC describes the required load supply, not automatically the permissible supply to the power supply. Before connecting, compare the terminal diagram, rating plate and data sheet of the exact type; do not infer the meaning of the voltage only from the short item name.
The manufacturer table RPS-45 distinguishes the input inrush current, overload protection and behaviour after overvoltage. This information does not give permission for arbitrary overloading. For the chosen type, separately verify the start-up of a capacitive load, any power reduction at higher temperature and the method of recovery after a fault. The operating temperature range alone does not guarantee full power over the entire interval.
Consider a hypothetical controller with a consumption of 0.2 A, a display 0.35 A and four output loads of 0.25 A each on a common 24 V branch. With simultaneous switching, the result is 1.55 A. If a communication device with a start-up consumption of 1 A for 200 ms is added, the design must handle a total of 2.55 A during this time. The values are model values, not data of specific Rievtech products.
The rated 2.5 A of the candidate is therefore not in itself confirmation of suitability. Verify the short-term mode, temperature and voltage directly at the controller. If the documentation does not cover the start-up profile, choose a sufficiently sized solution or adjust the simultaneity in a verified way. Do not rely on random timing of switch-on.
No. Verify the necessary protective separation and conditions of use in the documents of the exact type and in the design of the whole installation. A general short-circuit protection designation is not such a document.
The code alone without the manufacturer is not enough. Also compare the purpose, input, version and current documentation. A checklist for electrical wiring, mechanical mounting and protection is contained in the main guide Power supplies.
Necesitamos las cookies técnicas para que funcionen el carrito y el pedido — se usan siempre. Las cookies analíticas nos muestran qué páginas buscan las personas y dónde se pierden, y nos ayudan a mejorar la tienda. Solo las usaremos si nos lo permites. Más información en la política de tratamiento de datos.
Elige qué cookies podemos usar. Puedes cambiar tu elección en cualquier momento.
Guardan el contenido del carrito, el inicio de sesión y el idioma elegido, y protegen los formularios frente a abusos. Sin ellas no se puede finalizar el pedido, por eso se utilizan incluso sin consentimiento.
Google Analytics nos muestra de forma agregada el tráfico y el comportamiento en el sitio. Así sabemos qué páginas no funcionan para los usuarios. Con estos datos no identificamos a nadie.