Phone +420 774 723 123 Cart · 0 · empty
OUR TIP
CONVERTER-PT100, TECHNOLINE, converter for automation, 24V DC, 0–10 V, PT100

CONVERTER-PT100, TECHNOLINE, converter for automation, 24V DC, 0–10 V, PT100

Cat. no.: CONVERTER-PT100
Manufacturer: Čína
On request
Our price excl. VAT
12,26 €
incl. VAT 21 %
14,84 €
Recycling fee 5-32-1 (0,041 €/kg) 0,00 €
Weight 0.03 kg
HS Code (Taric) 85043129
Country of origin CN

Description

CONVERTER-PT100, TECHNOLINE, temperature converter PT100 to 0–10V, range -50 to +100°C, 24VDC

Sensor PT100 -50 to +100°C Output 0–10V Supply 24VDC

CONVERTER-PT100 is a temperature converter TECHNOLINEthat converts the signal of a resistance temperature sensor PT100 to an analogue voltage 0–10V. The converter has a calibrated measuring range -50 to +100°C and requires a supply of 24VDC.

IMPORTANT: MEASURING RANGE -50 to +100°C

A temperature of -50°C corresponds to an output of 0V and a temperature of +100°C output 10V. This assignment must be taken into account when configuring the analogue input of the control system.

Temperature conversion principle

The converter processes the resistance signal of the PT100 sensor and generates a corresponding analogue voltage 0–10V. This signal can be evaluated by a PLC or other control device equipped with an analogue voltage input.

For the measured temperature to be displayed correctly, the conversion of the output voltage to temperature must be set in the range -50 to +100°C.

The converter is equipped with adjustment potentiometers, which allow fine correction of the measurement deviation, for example due to the resistance of the PT100. sensor connecting lead

Technical specifications

Parameter Value
Order code CONVERTER-PT100
Manufacturer TECHNOLINE
Device type Temperature to analogue voltage converter
Input sensor PT100, resistance temperature sensor
Measuring range -50 to +100°C
Analogue output 0–10VDC
Conversion of limit values -50°C = 0V; +100°C = 10V
Supply voltage 24VDC
Adjustment option Fine correction using potentiometers

Setting the PLC analogue input

With linear scaling, the following applies for converting the output voltage to temperature:

Temperature [°C] = (voltage [V] × 15) - 50

Conversion examples:

Output voltage Corresponding temperature
0V -50°C
2V -20°C
5V +25°C
8V +70°C
10V +100°C

FAQ

What measuring range does the CONVERTER-PT100 converter have?

The CONVERTER-PT100 converter is calibrated for measuring temperatures from -50 to +100°C.

What output voltage corresponds to a temperature of 25°C?

At a temperature of 25°C the output voltage corresponding to the linear conversion is 5V.

What are the adjustment potentiometers for?

They allow fine tuning of the measurement, for example correction of a deviation caused by the PT100. sensor connecting cable

Technical parameters

Objednací kódCONVERTER-PT100
VýrobceČína

Downloads

Ask about this product

Ask us about technical parameters, compatibility with your equipment, availability or a price for larger quantities. It helps if you tell us what application you need the product for — if it does not fit, we will recommend a more suitable type.

Kód k opsání. Pokud ho nepřečtete, klikněte na Načíst nový kód.
The question relates to product CONVERTER-PT100

By sending you agree to the processing of the data provided for the purpose of handling your question. We do not pass the data on to third parties.

Related products

Cookies on this website

We need technical cookies for the cart and checkout to work — these are always used. Analytics cookies show us which pages people look for and where they get lost, and help us improve the shop. We only use them if you allow it. More in the data processing policy.