Ring-lug thermocouple 6mm, 3m, ETBSKP06-5.0C, Enda
Ring-lug thermocouple 6mm, 3m, ETBSKP06-5.0C, Enda
Tipo de cambio 24,43 Kč por 1 EUR. Los precios son orientativos; la facturación se realiza en coronas checas.
Enda temperature sensors – Pt100 probes and thermocouples with bayonet, ring-lug or threaded mounting for temperature controllers. Choose by sensor type, design and cable length.
Ring-lug thermocouple 6mm, 3m, ETBSKP06-5.0C, Enda
Pt100 element, EP0812-5.0C PT100, 3m, Enda
Pt100 element, EP0630-5.0C PT100, 3m, Enda
Los precios incluyen la tasa de reciclaje.
A temperature probe must match the controller input and the mounting method. A similar cable version may conceal a resistance element or a thermocouple, which require different measurement. When replacing, therefore, copy the complete code of the original probe, its dimensions and the set input type. A photograph of the termination alone does not prove electrical compatibility or suitability for the measured environment.
The public range includes ENDA EP0630-5.0C PT100, EP0812-5.0C PT100 and the ring-lug thermocouple ETBSKP06-5.0C. The manufacturer designates EP0630 as a bayonet resistance thermometer Pt100. It states a protective tube diameter of 6 mm and an insertion length of 30 mm. EP0812 according to the product sheet has a diameter of 8 mm and an insertion length of 12 mm. Both documents exclude use in liquids and humid environments.
A resistance sensor transmits a change in resistance; a thermocouple generates a thermoelectric voltage. For its evaluation, the temperature of the connection point is also essential, as explained by the WIKA manufacturer's explanation of the thermocouple principle. Do not consider the specific thermocouple type ETBSKP06 to be determined by mere assumption from the letters in the trade code. It must be confirmed by documentation for the given variant.
With a bayonet probe, check the seating of the tip and the function of the spring contact pressure.
If the tip does not rest against the intended measuring point, the control system may monitor different thermal conditions than the process engineer assumes. For a ring lug, describe the measured surface, fixing and lead routing. Do not confuse the mounting thread of the probe with the designation of the electrical connector just because both names begin with the letter M.
Before handover, prepare a sketch of the hole, stop and sensor position. For repeated replacements, use the same mounting procedure and record the actual position. Route the cable so that during maintenance it is not used as a handle for pulling out the probe and so that its movement does not change the contact of the measuring end.
Consider a purely educational linear thermoelectric model with a sensitivity of 40 microvolts per kelvin. The measuring point is at 100 °C and the connection point at 25 °C. A difference of 75 K corresponds to a model 3 000 microvolts. A device that interpreted this signal relative to zero without correct reference compensation would show 75 °C instead of 100 °C in this model.
The sensitivity is chosen for an illustrative calculation; it is not the characteristic or type of the ETBSKP06. offered. Real thermocouples have their own non-linear conversion tables. The example shows why a wiring or setting error should not be solved by randomly shifting the setpoint temperature in the controller.
Compare the sensor type, number of wires, permitted extension and break detection method with the input documentation. Then carry out a controlled temperature change and check that the reading changes in the correct direction. Separately verify the fault state with the probe disconnected. The record of the result should contain the reference instrument, measurement conditions and predetermined acceptance limits.
Other designs can be found in Temperature sensors. For comparing cable resistance probes, use TECHNOLINE temperature sensors.
Only if the device explicitly supports Pt100 and is correctly wired and configured for it. Matching terminals alone are not enough.
No. For the EP0630 and EP0812 described here, the manufacturer explicitly restricts the environment; the metal design does not cancel this condition.
Necesitamos las cookies técnicas para que funcionen el carrito y el pedido — se usan siempre. Las cookies analíticas nos muestran qué páginas buscan las personas y dónde se pierden, y nos ayudan a mejorar la tienda. Solo las usaremos si nos lo permites. Más información en la política de tratamiento de datos.
Elige qué cookies podemos usar. Puedes cambiar tu elección en cualquier momento.
Guardan el contenido del carrito, el inicio de sesión y el idioma elegido, y protegen los formularios frente a abusos. Sin ellas no se puede finalizar el pedido, por eso se utilizan incluso sin consentimiento.
Google Analytics nos muestra de forma agregada el tráfico y el comportamiento en el sitio. Así sabemos qué páginas no funcionan para los usuarios. Con estos datos no identificamos a nadie.